Free
Kenika UPS Online GH11
- Stock: In Stock
- Model: GH11
- Weight: 0.00kg
- Dimensions: 0.00cm x 0.00cm x 0.00cm
190 samples sold
Product Views: 7382
More from this brand
UPS KENIKA GH11 ini adalah UPS online. UPS online merupakan UPS yang paling lengkap proteksinya. UPS online menghasilkan tegangan output yang sangat stabil, tidak ada transfer time pada saat perpindahan dari listrik utama/PLN ke baterai, dan mempunyai gelombang sinus, sama seperti gelombang listrik yang dihasilkan oleh PLN.
Karena menghasilkan gelombang SINUS seperti gelombang yang dihasilkan listrik PLN maka UPS KENIKA GH11 sangat direkomendasikan untuk beban yang kritis seperti: peralatan laboratorium, peralatan kedokteran, server komputer atau beban kritis lainnya.
Specifications:
| MODEL | GH11 | |
| Capacity | 1000VA/800W | |
| INPUT | ||
| Voltage Range | Low Line Transfer | 85VAC/75VAC/65VAC/55VAC±5% or 160VAC/140VAC/120VAC/110VAC±5% (Ambient Temperature <35°C) (Based on Load Percentage 100% – 80% / 80% – 70% / 70% – 60% / 60% – 0) |
| Low Line Comeback | 95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ±5% (Ambient Temperature <35°C) (Based on Load Percentage 100% – 80% / 80% – 70% / 70% – 60% / 60% – 0) |
|
| High Line Transfer | 145VAC ±5% or 300VAC ±5% | |
| High Line Comeback | 140VAC ±5% or 290VAC ±5% | |
| Frequency Range | 40Hz ~ 70Hz | |
| Phase | Single Phase with Ground | |
| Power Factor | ≥ 0.99 @ Nominal Voltage (Input Voltage) | |
| OUTPUT | ||
| Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |
| AC Voltage Regulation | ±1% (Battery Mode) | |
| Frequency Range | 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) | |
| Frequency Range (Battery Mode) | 50Hz ± 0.25Hz or 60Hz ± 0.3Hz | |
| Overload | Ambient Temperature <35°C 105% ~ 110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal 110% ~ 130%: UPS shuts down after 1 minutes at battery mode or transfer to bypass when the utility is normal >130%: UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal |
|
| Current Crest Ratio | 3:1 | |
| Harmonic Distortion | ≤ 3% THD (Linear Load); ≤ 6% THD (Non-Linear Load) | |
| Transfer Time | AC Mode to Battery Mode | Zero |
| Inverter to Bypass | 4ms (Typical) | |
| Waveform (Battery Mode) | Pure Sinewave | |
| EFFICIENCY | ||
| AC Mode | 88% | |
| Battery Mode | 83% | |
| BATTERY | ||
| Battery Type | 12V 17Ah | |
| Battery Numbers | 3 | |
| Recharge Time | 4 Hours Recover to 90% Capacity (Typical) | |
| Charging Current | 1.0A (Max) | |
| Charging Voltage | 41.0VDC ± 1% | |
| PHYSICAL | ||
| Dimension (L×W×H) | 282×145×220 mm | |
| Box Dimension (L×W×H) | 360×230×325 mm | |
| Nett Weight | 4 kg | |
| Gross Weight | 5 kg | |
| BATTERY BANK | ||
| Dimension (L×W×H) | 193×282×233 mm | |
| Box Dimension (L×W×H) | 203×292×243 mm | |
| Nett Weight | 2 kg | |
| Gross Weight | 3.5 kg | |
| ENVIRONMENT | ||
| Operation Humidity | 20–90% RH @ 0~40°C (Non Condensing) | |
| Noise Level | Less than 50dBA @ 1 Meter | |
| MANAGEMENT | ||
| Smart RS-232 or USB | Support Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC | |
| Optional SNMP | Power Management from SNMP Manager and Web Browser | |